<< Click to Display Table of Contents >> Navigation: »No topics above this level« MpAlarmReset |
mapp Services V5.16
This function resets user-defined alarms.
Parameter |
Data type |
Description |
|
IN |
MpLink |
Connection to mapp configuration (MpLink of an MpAlarmBasic configuration) |
|
IN |
AlarmID |
UDINT |
User alarm ID (starts with 0) |
OUT |
Return value |
DINT |
Status information of function |
Section mapp components explains how mapp components are structured. In addition, it provides important notes for correctly using mapp components (e.g. for downloads).
Topics in this section: